Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 28, 2018, 11:46 AM
  • 01 1099_01 1098_8282018_045618.mp4

Date
08/28/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00210
PipeID
P01949
Time
4:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0959
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
20180828MDM_HUNTINGTON_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1099
Downstream MH
01 1098
Dir. of Survey
Downstream
Length Surveyed
301.8 ft.
Total Length
301.8 ft.
Structural Index
2
Structural Quick
3126
Structural Rating
15
O&M Index
3
O&M Quick
4111
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
20
Pipe schematic from manhole 01 1099 to 01 1098
MH: 01 1099MH: 01 1098downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:55AM8 ft. MGO - General Observation - 16" VCP16 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE25.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open65.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H65.5 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H77.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open125.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT125.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H125.1 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR126.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open174.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open226.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active275.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open287.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL295.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL301.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active301.8 ft. AMH - Downstream Manhole, Survey Ends - 5:20AM

Observation photos (1)

  • General Observation - 16" VCP

    8 ft. - General Observation - 16" VCP

Observations (20)

DistanceCodeObservation
125.1FCSLIGHT
25.2TFOpen
0MWM
0MWL
226.7TFActive
0AMH4:55AM
275.8TFOpen
16FLHAIRLINE
287.9FCSL
65.5FCH
65.5FCH
301.5MGOConn. @ Mh, 9 O' Clock. Active
125.1FCH
125.1RFJ
77.1TFOpen
126.1TFOpen
295.2FCSL
8MGO16" VCP
174.9TFOpen
301.8AMH5:20AM

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2018-08-28T04:46:23-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false