Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 28, 2018, 11:01 AM
  • 01 1101A_01 1101_8282018_040510.mp4

Date
08/28/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00210
PipeID
P01952
Time
4:01 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0959
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
20180828MDM_HUNTINGTON_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1101A
Downstream MH
01 1101
Dir. of Survey
Downstream
Length Surveyed
237.9 ft.
Total Length
237.9 ft.
Structural Index
2
Structural Quick
382A
Structural Rating
46
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
50
Pipe schematic from manhole 01 1101A to 01 1101
MH: 01 1101AMH: 01 1101downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:05AM8 ft. MGO - General Observation - 18" VCP9.9 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SLIGHT9.9 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL11 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open17.8 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H17.8 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H30.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE38.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H40.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, - SL43 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H43 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H50.6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H58.6 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H58.6 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H59.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open63.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H67.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open74.1 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H94.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H97.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H105.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H112.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H118.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open138.6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H163.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open195.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H211.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open237.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN237.9 ft. AMH - Downstream Manhole, Survey Ends - 4:30AM

Observation photos (2)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    30.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES,  - SL

    40.5 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, - SL

Observations (33)

DistanceCodeObservation
0MWM
0MGOConn. @ Mh, 9 O' Clock. Active
138.6FCH
30.5FLHAIRLINE
237.3MGOConn. @ Mh, 3 O' Clock. OPEN
9.9FCSLIGHT
211.9TFOpen
40.5FLSL
63.5FLH
43FLH
58.6FCH
8MGO18" VCP
0MWL
118.9TFOpen
58.6FCH
195.2FLH
74.1FCH
0AMH4:05AM
163.3TFOpen
50.6FCH
43FLH
237.9AMH4:30AM
9.9FCSL
112.5FLH
59.7TFOpen
38.2FLH
97.5FCH
67.3TFOpen
17.8FCH
11TFOpen
94.5FCH
105.4FLH
17.8FCH

Properties (6)

custom_field_three
LONG HAIRLINE FRACTURE JOINT TO JOINT
custom_field_two
3
customer
LACSD
datetime
2018-08-28T04:01:19-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false