- Date
- 08/27/2018
- W/O
- 0723688
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00210
- PipeID
- P01974
- Time
- 5:12 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0956
- Sewer Name
- 01 HUNTINGTON PARK TRUNK
- City
- HUNTINGTON PARK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- 20180827MDM_HUNTINGTON_PARK_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 01 1121
- Downstream MH
- 01 1122
- Dir. of Survey
- Upstream
- Length Surveyed
- 270.9 ft.
- Total Length
- 270.9 ft.
- Structural Index
- 3
- Structural Quick
- 3B22
- Structural Rating
- 52
- O&M Index
- 2
- O&M Quick
- 3325
- O&M Rating
- 19
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 71
Pipe schematic from manhole 01 1121 to 01 1122 Observation photos (2)

8 ft. - General Observation - 15" VCP

174 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 35 %, within 8 inches of joint: YES