Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2018, 09:59 AM
  • 01 1114_01 1113_8202018_031630.mp4

Date
08/20/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00210
PipeID
P01965
Time
2:59 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0952
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTING PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
20180820MDM_HUNTINGTON_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1114
Downstream MH
01 1113
Dir. of Survey
Downstream
Length Surveyed
312.7 ft.
Total Length
312.7 ft.
Structural Index
3
Structural Quick
3B25
Structural Rating
55
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
59
Pipe schematic from manhole 01 1114 to 01 1113
MH: 01 1114MH: 01 1113downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 3:00AM2.5 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT6.2 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - H8 ft. MGO - General Observation - 18" VCP9.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H10.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open11.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H11.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H17.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H19.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H40 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL50.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL59.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open66.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open72 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped79 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H86.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H90.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open99.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, 6ft - Open112.4 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H112.4 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H115.3 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 5" - Open121.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open126.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped129 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped140.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL152.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active158.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H165.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped170.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open175.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open179.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H206 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open213.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, 6ft - SL216.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped249.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL260.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open263.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped269.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H309.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open312.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active312.7 ft. AMH - Downstream Manhole, Survey Ends - 3:25AM

Observation photos (1)

  • General Observation - 18" VCP

    8 ft. - General Observation - 18" VCP

Observations (45)

DistanceCodeObservation
112.4FLH
40FLSL
99.9FLOpen
269.8FLH
59.4TFOpen
17.1FCH
312.3MGOConn. @ Mh, 9 O' Clock. Active
112.4FLH
66.9TFOpen
249.2FLSL
312.7AMH3:25AM
0MWL
121.2TBOpen
2.5FCSLIGHT
11.4FCH
50.3FLSL
165.1TFCCapped
115.3TBOpen
140.9FCSL
179.6FLH
216.6TFCCapped
158.8FLH
170.5TBOpen
126.6TFCCapped
79FLH
6.2FCH
0MWM
72TFCCapped
11.4FLH
8MGO18" VCP
309.7TFOpen
260.9TFOpen
9.3FLH
0MGOConn. @ Mh, 9 O' Clock. Active
19.1FLH
10.3TFOpen
175.6TFOpen
0AMH3:00AM
206TBOpen
152.6TBActive
86.7FLH
213.6FLSL
129TFCCapped
90.6TBOpen
263.2TFCCapped

Properties (6)

custom_field_three
SLIGHT & HAIRLINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2018-08-20T02:59:52-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection