Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2018, 09:20 AM
  • 01 1115_01 1114_8202018_023747.mp4

Date
08/20/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00210
PipeID
P01966
Time
2:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0952
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTING PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
20180820MDM_HUNTINGTON_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1115
Downstream MH
01 1114
Dir. of Survey
Downstream
Length Surveyed
202.8 ft.
Total Length
202.8 ft.
Structural Index
3
Structural Quick
3A26
Structural Rating
48
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
52
Pipe schematic from manhole 01 1115 to 01 1114
MH: 01 1115MH: 01 1114downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWM - Water Mark, 60 %of cross sectional area6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SLIGHT8 ft. MGO - General Observation - 18" VCP8.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE14.2 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - SL22.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H25.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open51.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open51.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H54.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped60.8 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H60.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H65.6 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H65.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H71.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open91.8 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H96.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H100.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped102.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open107.1 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H109.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H119.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H123.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open135.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHHT138.2 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H152 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped162.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active169.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL182.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H202.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active202.8 ft. AMH - Downstream Manhole, Survey Ends - 2:45AM

Observation photos (1)

  • General Observation - 18" VCP

    8 ft. - General Observation - 18" VCP

Observations (34)

DistanceCodeObservation
51.2TBOpen
0MWL
0AMH2:25AM
6FLSLIGHT
0MGOConn. @ Mh, 9 O' Clock. Active
14.2FCSL
71.8TFOpen
91.8FCH
162.9TFActive
202.4MGOConn. @ Mh, 9 O' Clock. Active
109.7FLH
152TFCCapped
182.3FLH
169.5FLSL
60.8FCH
123.8TFOpen
119.9FLH
100.6TFCCapped
60.8FLH
135.3FLSLIGHHT
22.4FLH
25.7TFOpen
102.5TBOpen
54.2TFCCapped
51.2FLH
0MWM
65.6FCH
8.8FLHAIRLINE
107.1FCH
96.9FLH
138.2FCH
65.6FLH
8MGO18" VCP
202.8AMH2:45AM

Properties (6)

custom_field_three
SLIGHT & HAIRLINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2018-08-20T02:20:00-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false