Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2018, 07:40 AM
  • 01 1117_01 1116_8202018_005322.mp4

Date
08/20/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00210
PipeID
P01968
Time
12:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0952
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTING PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
20180820MDM_HUNTINGTON_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1116
Downstream MH
01 1117
Dir. of Survey
Upstream
Length Surveyed
187.8 ft.
Total Length
187.8 ft.
Structural Index
3
Structural Quick
3A29
Structural Rating
51
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
51
Pipe schematic from manhole 01 1116 to 01 1117
MH: 01 1116MH: 01 1117upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:15AM0.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0.5 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. Active8.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H47.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H50.7 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL51.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped57.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 5" - Open59.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open60.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H73.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL77.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H83.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H97.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H101.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped105.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL106.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open112 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open115.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H134 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H138.8 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H147 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H150.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped158 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H158 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H158.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open162.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL173 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H175.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SLIGHT179.7 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H179.8 ft. MGO - General Observation - 18" VCP181.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - HAIRLINE187.8 ft. AMH - Downstream Manhole, Survey Begins - 12:50AM187.8 ft. MWM - Water Mark, 40 %of cross sectional area187.8 ft. MWL - Water Level, 20 %of cross sectional area

Observations (36)

DistanceCodeObservation
75.8TFOpen
25.3FCSL
40.8FLH
86.6TFCCapped
8.1FLH
110.6FCH
0AMH12:50AM
29.8FCH
187.3MGOConn. @ Mh, 9 O' Clock. Capped
187.3MGOConn. @ Mh, 12 O' Clock. Active
127.3FLH
37TFCCapped
130.4TFOpen
29.8FLH
137.1FCSL
187.8AMH1:15AM
90.7FLH
179.3TFCCapped
0MWM
72.1FLH
136TFCCapped
49FCH
104FCH
8MGO18" VCP
178.8FCH
81.9FLSL
0MWL
12.2FLSLIGHT
29TFOpen
14.8FCH
81.3TFOpen
53.8FLH
114.6FCSL
127.9TFOpen
139.9FLH
6FLHAIRLINE

Properties (6)

custom_field_three
SLIGHT & HAIRLINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2018-08-20T00:40:12-07:00
documentation
MARTIN,REVELES,OLIVER 111,YOUNG
is_lateral_inspection
false