Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2018, 09:45 AM
  • 01 1109_01 1108_8242018_024801.mp4

Date
08/24/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
Reveles
Sewer ID
Z00210
PipeID
P01959
Time
2:45 AM
Certificate
U-115-06022633
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0953
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK TRUNK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
08242018ROIII_Huntington_Park_Trunk
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1109
Downstream MH
01 1108
Dir. of Survey
Downstream
Length Surveyed
303.3 ft.
Total Length
303.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4222
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 1109 to 01 1108
MH: 01 1109MH: 01 1108downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02:48 AM2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES, Start2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Start4.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"10.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open49.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open100.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open152.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open201 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open239.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open285.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open285.7 ft. RMB - Roots Medium Barrell, at 02 o'clock, 15 %, within 8 inches of joint: YES290.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"301.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES, Finish301.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Finish303.3 ft. AMH - Downstream Manhole, Survey Ends - 03:10 AM

Observation photos (1)

  • Roots Medium Barrell, at 02 o'clock, 15 %, within 8 inches of joint: YES

    285.7 ft. - Roots Medium Barrell, at 02 o'clock, 15 %, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
239.5TFOpen
152.1TFOpen
49.1TFOpen
0MWL
290.8TFC
0MWM
100.5TFOpen
10.5TFOpen
285.7TFOpen
4.4TBA
2.9DAGS
0AMH02:48 AM
301.1DAGS
301.1DAGS
2.9DAGS
285.7RMB
303.3AMH03:10 AM
201TFOpen

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2018-08-24T02:45:20-07:00
documentation
Reveles, Oliver III
is_lateral_inspection
false