Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2018, 07:03 AM
  • 01 1111_01 1110_8242018_002912.mp4

Date
08/24/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
Oliver III
Sewer ID
Z00210
PipeID
P01961
Time
12:03 AM
Certificate
U-415-06024036
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0953
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK TRUNK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
08242018ROIII_Huntington_Park_Trunk
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1110
Downstream MH
01 1111
Dir. of Survey
Upstream
Length Surveyed
309 ft.
Total Length
309 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 1110 to 01 1111
MH: 01 1110MH: 01 1111upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:57am0 ft. TFD - Tap Factory Made Defective, at 03 o'clock, -, within 8 inches of joint: NO, 8" - Connectopm 100% covered with mud4.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Finish4.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Finish30.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open67.7 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES75.8 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open78.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"79.3 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open125 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open129.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"131.8 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 3" - Open176.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open225.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open261.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open273.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Start273.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start274.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"294.6 ft. CM - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES309 ft. AMH - Downstream Manhole, Survey Begins - 1220 am309 ft. MWM - Water Mark, 40 %of cross sectional area309 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (3)

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 3" - Open

    177.2 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 3" - Open

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open

    184 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open

    229.7 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open

Observations (22)

DistanceCodeObservation
184TBOpen
309AMH1:57am
278.7TFOpen
34.2TFA
230.6TFC
47.4TFOpen
14.4CM
304.9DAGS
0AMH1220 am
229.7TBOpen
179.1TFC
35.3DAGS
132.7TFOpen
0MWM
233.2TBOpen
0MWL
309TFDConnectopm 100% covered with mud
35.3DAGS
241.3CM
304.9DAGS
83.7TFOpen
177.2TBOpen

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2018-08-24T00:03:00-07:00
documentation
Reveles, Oliver III
is_lateral_inspection
false