Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 26, 2018, 09:55 AM
  • 16 0323_16 0322_9262018_025842.mp4

Date
09/26/2018
W/O
0729304
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00665
PipeID
P13374
Time
2:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0983
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20180921MDM_SAN_MARINO_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
16 0323
Downstream MH
16 0322
Dir. of Survey
Downstream
Length Surveyed
227.6 ft.
Total Length
227.6 ft.
Structural Index
2
Structural Quick
342A
Structural Rating
32
O&M Index
2
O&M Quick
3223
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
45
Pipe schematic from manhole 16 0323 to 16 0322
MH: 16 0323MH: 16 0322downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM0 ft. MWL - Water Level, 10 %of cross sectional area4 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT8 ft. MGO - General Observation - 15" VCP20.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL25.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE28.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL28.1 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H30.4 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL30.4 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - H33 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL35.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL35.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL37 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6" - Capped39.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open40.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS40.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS40.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS40.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS62.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open87.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped136.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open138.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped173.9 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR - 3%185 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6", 6" - Open-80% ROOTS185 ft. RML - Roots Medium Lateral, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES187.6 ft. RML - Roots Medium Lateral, from 08 to 09 o'clock, 5 %, within 8 inches of joint: YES187.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% ROOTS193.8 ft. RFB - Roots Fine Barrell, from 03 to 09 o'clock, within 8 inches of joint: YES - 3%227 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% HAIRLINE AT JOINTS227 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active227 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% SLIGHT AT JOINTS227 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 15% HAIRLINE AT JOINTS227 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS227.6 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observations (36)

DistanceCodeObservation
37TFCCapped
25.3FLHAIRLINE
4FCSLIGHT
30.4FCSL
0MWM
8MGO15" VCP
30.4FCH
20.3FCSL
227FC40% HAIRLINE AT JOINTS
39.2TFOpen
136.4TFOpen
138.7TFCCapped
227.6AMH3:20AM
40.7FCSLIGHT AT JOINTS
0AMH2:45AM
87.8TFCCapped
173.9RFJ3%
40.7FLHAIRLINE AT JOINTS
40.7FLSLIGHT AT JOINTS
185TFDOpen-80% ROOTS
227MGOConn. @ Mh, 9 O' Clock. Active
28.1FCSL
187.6RML
35.6FLSL
62.2TFOpen
35.6FCSL
33FCSL
28.1FCH
227FC40% SLIGHT AT JOINTS
227FL15% HAIRLINE AT JOINTS
193.8RFB3%
185RML
0MWL
40.7FCHAIRLINE AT JOINTS
187.6TFDOpen-80% ROOTS
227FL10% SLIGHT AT JOINTS

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-09-26T02:55:00-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false