Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 25, 2018, 08:37 AM
  • 16 0351_16 0350_9252018_020854.mp4

Date
09/25/2018
W/O
0729304
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00665
PipeID
P13402
Time
1:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0982
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20180921MDM_SAN_MARINO_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
16 0351
Downstream MH
16 0350
Dir. of Survey
Downstream
Length Surveyed
217.7 ft.
Total Length
217.7 ft.
Structural Index
2
Structural Quick
322A
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
30
Pipe schematic from manhole 16 0351 to 16 0350
MH: 16 0351MH: 16 0350downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM8 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT8 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL10.5 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL10.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL13.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE18.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL18.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H23.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL25.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL30.6 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL35.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS35.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS35.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS35.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS75.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped146.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped213.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped217.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 15% HAIRLINE AT JOINTS217.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% HAIRLINE AT JOINTS217.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% SLIGHT AT JOINTS217.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 155 SLIGHT AT JOINTS217.7 ft. AMH - Downstream Manhole, Survey Ends - 2:40AM

Observations (25)

DistanceCodeObservation
75.1TFCCapped
0MWL
18.2FCSL
10.5FCSL
10.5FCSL
217.2FL15% HAIRLINE AT JOINTS
35.7FCHAIRLINE AT JOINTS
0MWM
8FCSLIGHT
18.2FCH
35.7FCSLIGHT AT JOINTS
35.7FLHAIRLINE AT JOINTS
25.8FCSL
0AMH2:10AM
217.2FC60% HAIRLINE AT JOINTS
213.9TFCCapped
30.6FCSL
217.7AMH2:40AM
217.2FC40% SLIGHT AT JOINTS
146.2TFCCapped
13.1FCHAIRLINE
8FCSL
23.3FCSL
217.2FL155 SLIGHT AT JOINTS
35.7FLSLIGHT AT JOINTS

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-09-25T01:37:44-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false