Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2018, 07:36 AM
  • 16 0353_16 0352_9242018_042051.mp4

Date
09/24/2018
W/O
0729304
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00665
PipeID
P13404
Time
12:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0981
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Capital Improvement Program Assesment
Project
20180921MDM_SAN_MARINO_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
14 in.
Upstream MH
16 0353
Downstream MH
16 0352
Dir. of Survey
Downstream
Length Surveyed
284.6 ft.
Total Length
284.6 ft.
Structural Index
2
Structural Quick
322B
Structural Rating
36
O&M Index
2
O&M Quick
3521
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
56
Pipe schematic from manhole 16 0353 to 16 0352
MH: 16 0353MH: 16 0352downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MWM - Water Mark, 30 %of cross sectional area4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT7.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL8.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-60% GREASE9.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL10.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open12.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL12.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE14.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H14.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL17 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL17 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL19.7 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL19.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL22.1 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL24.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL27.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS27.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS27.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS27.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS103.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open105.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active116.9 ft. RMJ - Roots Medium Joint, from 04 to 05 o'clock, 5 %, within 8 inches of joint: YESR124.3 ft. RFJ - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YESR - 3%131.9 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YESR - 3%162.5 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR - 4%162.9 ft. RMJ - Roots Medium Joint, from 04 to 08 o'clock, 10 %, within 8 inches of joint: YESR203.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped206.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open211.8 ft. RMJ - Roots Medium Joint, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YESR219.1 ft. RMJ - Roots Medium Joint, from 08 to 10 o'clock, 5 %, within 8 inches of joint: YESR254.2 ft. RMJ - Roots Medium Joint, from 03 to 04 o'clock, 5 %, within 8 inches of joint: YESR282.7 ft. MGO - General Observation - SHELVES IN MH CORRODED SEVERE284 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% SLIGHT AT JOINTS284 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 15% SLIGHT AT JOINTS284 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 15% HAIRLINE AT JOINTS284 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE AT JOINTS284 ft. MGO - General Observation - SHELVES CORRODED SEVERE284.6 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (2)

  • General Observation - SHELVES IN MH CORRODED  SEVERE

    282.7 ft. - General Observation - SHELVES IN MH CORRODED SEVERE

  • General Observation - SHELVES CORRODED SEVERE

    284 ft. - General Observation - SHELVES CORRODED SEVERE

Observations (41)

DistanceCodeObservation
17FCSL
0MWL
10.7TFOpen
4FCSLIGHT
162.5RFJ4%
203.7TFCCapped
284FC70% SLIGHT AT JOINTS
131.9RFJ3%
103.2TFOpen
0AMH4:25AM
27.3FLHAIRLINE AT JOINTS
284FL15% SLIGHT AT JOINTS
27.3FCSLIGHT AT JOINTS
284FL15% HAIRLINE AT JOINTS
22.1FCSL
211.8RMJ
17FCSL
8.1TFDOpen-60% GREASE
14.5FCH
282.7MGOSHELVES IN MH CORRODED SEVERE
254.2RMJ
27.3FCHAIRLINE AT JOINTS
19.7FCSL
162.9RMJ
14.5FCSL
284.6AMH5:00AM
12.2FCSL
0MWM
116.9RMJ
124.3RFJ3%
12.2FCHAIRLINE
105.8TFActive
27.3FLSLIGHT AT JOINTS
284FC50% HAIRLINE AT JOINTS
284MGOSHELVES CORRODED SEVERE
219.1RMJ
9.4FCSL
206.1TFOpen
19.7FCSL
24.3FCSL
7.5FCSL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-09-24T00:36:06-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false