Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2018, 06:40 PM
  • H 0402_H 0401A_9202018_114527.mp4

Date
09/20/2018
W/O
0729413
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00177
PipeID
P22747
Time
11:40 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7813
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20180920DF_JOINT_OUTFALL_H_UNIT_5A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
H 0402
Downstream MH
H 0401A
Dir. of Survey
Downstream
Length Surveyed
22 ft.
Total Length
22 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole H 0402 to H 0401A
MH: H 0402MH: H 0401Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 11:44 AM0.1 ft. MWL - Water Level, 30 %of cross sectional area0.1 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 30% MAG8.1 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start8.1 ft. MGP - General Photograph11.7 ft. MGP - General Photograph20.5 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 30% MAG20.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.5 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Finish20.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.5 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish21 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach21 ft. MGP - General Photograph - GREASE THROUGHOUT THE REACH (5%)22 ft. AMH - Downstream Manhole, Survey Ends - 12:00 PM

Observation photos (12)

  • Upstream Manhole, Survey Begins - 11:44 AM

    0 ft. - Upstream Manhole, Survey Begins - 11:44 AM

  • Water Mark, 35 %of cross sectional area

    0.1 ft. - Water Mark, 35 %of cross sectional area

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 30% MAG

    2.3 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 30% MAG

  • Deposits Attached Ragging, 5 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: YES, Start

    8.1 ft. - Deposits Attached Ragging, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start

  • General Photograph

    8.1 ft. - General Photograph

  • General Photograph

    11.7 ft. - General Photograph

  • Deposits Attached Ragging, 5 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: YES, Finish

    20.5 ft. - Deposits Attached Ragging, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Finish

Observations (22)

DistanceCodeObservation
20.5SZ30% MAG
20.5SAV
20.5DAR
20.5SSS
2SAP
20.5SAP
21MGOPeeling & Flaking Throughout The Reach
8.1DAR
11.7MGP
0.1MWL
2.1SRV
22AMH12:00 PM
2SAV
0.1MWM
20.5SRC
2SSS
21MGPGREASE THROUGHOUT THE REACH (5%)
2SRC
2.3SZ30% MAG
20.5SRV
8.1MGP
0AMH11:44 AM

Properties (6)

custom_field_two
2
customer
LACSD
datetime
2018-09-20T11:40:31-07:00
documentation
FRANKLIN, IGNACIO, PARAISO, VENDRYES
is_lateral_inspection
false
year_laid
20000828