Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2018, 05:47 PM
  • E 0110_E 0109_9242018_105805.mp4

Date
09/24/2018
W/O
0730604
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00032
PipeID
P11336
Time
10:47 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7816
Sewer Name
E JOINT OUTFALL E - UNIT 5
City
LOS ANGELES
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
20180920DF_JOINT_OUTFALL_E_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
E 0109
Downstream MH
E 0110
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
4
Overall Quick
Overall Rating
17
Pipe schematic from manhole E 0109 to E 0110
MH: E 0109MH: E 0110upstream0 ft. MSA - Survey Abandoned - 11:04 AM0 ft. LD - Alignment Down, 45 %0.1 ft. MGO - General Observation - ROACHES0.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 70% MAG0.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. MGP - General Photograph0.1 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach2.1 ft. AMH - Downstream Manhole, Survey Begins - 10:56 AM2.1 ft. MWL - Water Level, 100 %of cross sectional area2.1 ft. MWM - Water Mark, 100 %of cross sectional area

Observation photos (7)

  • Water Mark, 100 %of cross sectional area

    0 ft. - Water Mark, 100 %of cross sectional area

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 70% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 70% MAG

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph

    2 ft. - General Photograph

  • General Observation - Peeling & Flaking Throughout The Reach

    2 ft. - General Observation - Peeling & Flaking Throughout The Reach

  • Alignment Down, 45 %

    2.1 ft. - Alignment Down, 45 %

Observations (11)

DistanceCodeObservation
2MGOROACHES
2SAV
2SZ70% MAG
2.1MSA11:04 AM
2SRV
2.1LD
2MGP
0AMH10:56 AM
0MWL
2MGOPeeling & Flaking Throughout The Reach
0MWM

Properties (6)

additional_info
VIEW OF THE UPLEG FROM THE D/S SIPHON
custom_field_two
5
customer
LACSD
datetime
2018-09-24T10:47:42-07:00
documentation
FRANKLIN, VENDRYES, PARAISO, YOUNG
is_lateral_inspection
false