Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2018, 03:18 PM
  • E 0110_E 0109_9242018_082940.mp4

  • E 0110_E 0109_9242018_095140.mp4

Date
09/24/2018
W/O
0730604
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00032
PipeID
P11336
Time
8:18 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7816
Sewer Name
E JOINT OUTFALL E - UNIT 5
City
LOS ANGELES
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
20180920DF_JOINT_OUTFALL_E_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
E 0110
Downstream MH
E 0109
Dir. of Survey
Downstream
Length Surveyed
430 ft.
Total Length
430 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole E 0110 to E 0109
MH: E 0110MH: E 0109downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:20 AM0 ft. MGP - General Photograph0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.1 ft. MGP - General Photograph18.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.6 ft. MGP - General Photograph - AGGREGATE31.7 ft. MGP - General Photograph95 ft. MGP - General Photograph180.8 ft. MGP - General Photograph360.4 ft. MGP - General Photograph420.4 ft. MGP - General Photograph428.4 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 55% MAG428.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish428.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish428.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish430 ft. AMH - Downstream Manhole, Survey Ends - 9:56 AM430 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach430 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (11)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 55% MAG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    8.1 ft. - General Photograph

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - AGGREGATE

    31.6 ft. - General Photograph - AGGREGATE

  • General Photograph

    31.7 ft. - General Photograph

  • General Photograph

    95 ft. - General Photograph

  • General Photograph

    180.8 ft. - General Photograph

  • General Photograph

    360.4 ft. - General Photograph

  • General Photograph

    420.4 ft. - General Photograph

Observations (22)

DistanceCodeObservation
31.7MGP
0MWM
180.8MGP
430AMH9:56 AM
428.4SZ55% MAG
95MGP
0AMH8:20 AM
31.6MGPAGGREGATE
420.4MGP
428.4SRV
428.4SAV
0MGP
360.4MGP
2SZ55% MAG
2SSS
0MWL
2SAV
430MGOPeeling & Flaking Throughout The Reach
18.1SRV
8.1MGP
430MGOGREASE THROUGHOUT THE REACH (5%)
428.4SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2018-09-24T08:18:21-07:00
documentation
FRANKLIN, VENDRYES, PARAISO, YOUNG
is_lateral_inspection
false