Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2017, 10:32 AM
  • C 0119B_A 0247_24072017_033352.mp4

Date
07/24/2017
W/O
635398
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00127
PipeID
P09642
Time
3:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4757
Sewer Name
C JOINT OUTFALL C - UNIT 4B
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
20
Purpose
Routine Assessment
Project
WO_635398_TV03074_JUN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
C 0119B
Downstream MH
A 0247
Dir. of Survey
Downstream
Length Surveyed
16.5 ft.
Total Length
16.5 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole C 0119B to A 0247
MH: C 0119BMH: A 0247downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 0119B0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.3 ft. MGO - General Observation - MAG COAT4.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.4 ft. SRV - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES16.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK16.5 ft. AMH - Downstream Manhole, Survey Ends - A 024716.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish16.5 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

    10.4 ft. - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0AMHC 0119B
4.4SAP
16.5MGOCONNECTION AT MH 9 O'CLOCK
0MWL
10.4SRV
16.5AMHA 0247
2.3MGOMAG COAT
16.5SAP
16.5MGOCONNECTION AT MH 12 O'CLOCK
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (5)

additional_info
SC345517
custom_field_two
2
customer
LACSD
datetime
2017-07-24T03:32:07-07:00
is_lateral_inspection
false