Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2018, 10:36 AM
  • C 0119_C 0118_522018_034902.mp4

Date
05/02/2018
W/O
0694536
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00127
PipeID
P09639
Time
3:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0850
Sewer Name
C JOINT OUTFALL C - UNIT 4B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
20
Purpose
Routine Assessment
Project
20180502MDM_JOINT_OUTFALL_C_UNIT_4B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
C 0119
Downstream MH
C 0118
Dir. of Survey
Downstream
Length Surveyed
108.9 ft.
Total Length
108.9 ft.
Structural Index
4
Structural Quick
5241
Structural Rating
25
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
25
Pipe schematic from manhole C 0119 to C 0118
MH: C 0119MH: C 0118downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM0 ft. MWL - Water Level, 20 %of cross sectional area - NO FLOW FLOATING SLUDGE0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR7.9 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR BROKEN10.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG10.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CURCUM REBAR10.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR10.8 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG12 ft. MGO - General Observation - 48" RCP26.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE70.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active85 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES FINISH - SEVERE AGG85 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG VERY SPORATIC108.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG VERY SPORATIC108.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE108.9 ft. MSA - Survey Abandoned - 4:15AM FLOATING SLUDGE

Observation photos (9)

  • Water Level, 20 %of cross sectional area - NO FLOW FLOATING SLUDGE

    0 ft. - Water Level, 20 %of cross sectional area - NO FLOW FLOATING SLUDGE

  • General Observation - Conn. @ Mh, 3 O' Clock. OPEN

    0 ft. - General Observation - Conn. @ Mh, 3 O' Clock. OPEN

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES,  - CIRCUM REBAR BROKEN

    7.9 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR BROKEN

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    10.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 48" RCP

    12 ft. - General Observation - 48" RCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    26.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG VERY SPORATIC

    85 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG VERY SPORATIC

Observations (20)

DistanceCodeObservation
0MGOConn. @ Mh, 9 O' Clock. OPEN
0AMH3:40AM
12MGO48" RCP
0MWLNO FLOW FLOATING SLUDGE
70.3TFActive
7.9SRCCIRCUM REBAR BROKEN
2SAMSEVERE AGG
10.8SAPSEVERE AGG
0MWM
26.7SSSBLISTERING PEELING CONCRETE
108.9MSA4:15AM FLOATING SLUDGE
85SAPSEVERE AGG
85SAVSEVERE AGG VERY SPORATIC
108.7SAVSEVERE AGG VERY SPORATIC
108.7SSSBLISTERING PEELING CONCRETE
2SRCLONG CIRCUM REBAR
10.8SRCLONG CURCUM REBAR
10.8SRCLONG CIRCUM REBAR
10.8SAMSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. OPEN

Properties (5)

custom_field_three
CORRODED REBAR BROKEN
custom_field_two
1
customer
LACSD
datetime
2018-05-02T03:36:17-07:00
is_lateral_inspection
false