Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2017, 10:14 AM
  • B 1517_B 1516 _11122017_021855.mp4

Date
12/11/2017
W/O
673959
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01124
PipeID
P25631
Time
2:14 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5270
Sewer Name
B JOINT OUTFALL B - UNIT 6G
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
23
Purpose
Routine Assessment
Project
WO_673959_TV16038_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
B 1517
Downstream MH
B 1516
Dir. of Survey
Downstream
Length Surveyed
39.5 ft.
Total Length
39.5 ft.
Structural Index
2
Structural Quick
2700
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole B 1517 to B 1516
MH: B 1517MH: B 1516downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 15174.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish39.5 ft. AMH - Downstream Manhole, Survey Ends - B 151639.5 ft. MGO - General Observation - CONNECTION AT MH 8 O'CLOCK

Observation photos (1)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
39.5AMHB 1516
39.4SSS
0MWL
4.6SSS
39.5MGOCONNECTION AT MH 8 O'CLOCK
0AMHB 1517

Properties (7)

additional_info
SC346297
custom_field_two
3
customer
LACSD
datetime
2017-12-11T02:14:54-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
38886