Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 17, 2018, 08:02 AM
  • 05 1727_05 1726_10172018_010905.mp4

Date
10/17/2018
W/O
0734495
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00471
PipeID
P06954
Time
1:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1016
Sewer Name
05 LOMITA TRUNK
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Capital Improvement Program Assesment
Project
20181012MDM_LOMITA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1726
Downstream MH
05 1727
Dir. of Survey
Upstream
Length Surveyed
329.3 ft.
Total Length
329.3 ft.
Structural Index
3
Structural Quick
3A25
Structural Rating
46
O&M Index
3
O&M Quick
4221
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
56
Pipe schematic from manhole 05 1726 to 05 1727
MH: 05 1726MH: 05 1727upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:00AM3.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - SL10.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - SL27.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL50.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL58.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H62.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - SL62.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - SL67.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL78.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL78.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H78.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H78.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL91 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL127.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL134.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H187 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H187 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H197.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - H197.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - S215.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H216.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT216.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H219.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES219.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open237.8 ft. MWL - Water Level, 30 %of cross sectional area237.8 ft. MWM - Water Mark, 50 %of cross sectional area252.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - H252.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - H267.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H267.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - HAIRLINE301.9 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE321.3 ft. MGP - General Photograph - 21" VCP329.3 ft. MWL - Water Level, 40 %of cross sectional area329.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped329.3 ft. AMH - Downstream Manhole, Survey Begins - 1:05AM329.3 ft. MWM - Water Mark, 60 %of cross sectional area

Observation photos (12)

  • General Photograph - 21" VCP

    8 ft. - General Photograph - 21" VCP

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H

    61.8 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    61.8 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Water Mark, 50 %of cross sectional area

    91.5 ft. - Water Mark, 50 %of cross sectional area

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    112.8 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H

    113.5 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

    142.3 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

    142.3 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

    250.7 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

    250.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

    279.2 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

    302 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - SL

Observations (37)

DistanceCodeObservation
0MWL
61.8FLH
262FCSL
0MGOConn. @ Mh, 3 O' Clock. Capped
91.5MWL
329.3AMH2:00AM
271.2FCH
8MGP21" VCP
195FCH
266.4FLSL
109.5DAGS
250.7FLSL
318.6FLSL
131.9FLH
238.3FLSL
326.1FLSL
27.4FCHAIRLINE
250.7FLH
91.5MWM
142.3FLH
302FLSL
201.9FLSL
0AMH1:05AM
250.7FLH
109.5TFOpen
76.8FLH
0MWM
112.8FLSLIGHT
61.8FLHAIRLINE
131.9FLS
250.7FLSL
266.4FLSL
113.5FLH
279.2FLSL
112.8FCH
76.8FLH
142.3FLH

Properties (7)

additional_info
REVERSE INSPECTION
custom_field_three
SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2018-10-17T01:02:01-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false