Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 30, 2018, 05:47 PM
  • 05 1179_05 1178_7302018_104955.mp4

Date
07/30/2018
W/O
0717904
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00514
PipeID
P06417
Time
10:47 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7771
Sewer Name
05 ROSECRANS AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20180730SHO_ROSECRANS_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
11.300000190734863 in.
Upstream MH
05 1179
Downstream MH
05 1178
Dir. of Survey
Downstream
Length Surveyed
316.7 ft.
Total Length
316.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 1179 to 05 1178
MH: 05 1179MH: 05 1178downstream0 ft. AMH - Upstream Manhole, Survey Begins - MH 11790 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION IN THE MH @ 90 ft. MWM - Water Mark, 30 %of cross sectional area23.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start69.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"75.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"122.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6", 6"124.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"172.5 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6"175.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"222.4 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6"225 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"275.6 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: NO, 6"277.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"313.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish316.7 ft. AMH - Downstream Manhole, Survey Ends - MH 1178

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    23.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0AMHMH 1179
75.1TF
316.7AMHMH 1178
124.8TF
313.7DAGS
277.5TF
225TF
222.4TFD
0MWL
275.6TFD
175.4TF
122.2TF
0MGOACTIVE CONNECTION IN THE MH @ 9
172.5TFD
0MWM
69.7TF
23.2DAGS

Properties (6)

custom_field_three
LINER IS IN GOOD CONDITION
custom_field_two
4
customer
LACSD
datetime
2018-07-30T10:47:45-07:00
documentation
OBREGON, BRAR, PARAISO
is_lateral_inspection
false