Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 16, 2018, 10:46 AM
  • Section#6_H 0112_H 0111__1162018__G6919.mp4

Date
01/16/2018
W/O
0683963
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00165
PipeID
P10563
Time
2:46 AM
Certificate
U-101406022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6919
Sewer Name
H JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20180113MDM_JOINT_OUTFALL_H_UNIT_1F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
H 0112
Downstream MH
H 0111
Dir. of Survey
Downstream
Length Surveyed
491.8 ft.
Total Length
491.8 ft.
Structural Index
2
Structural Quick
332S
Structural Rating
207
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
207
Pipe schematic from manhole H 0112 to H 0111
MH: H 0112MH: H 0111downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE2 ft. MGO - General Observation - MAG COAT 80% START 8:00 TO 4:00165.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - SWOLLEN BLISTERING CONCRETE394.6 ft. SAP - Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG428 ft. SAV - Surface Aggregate Visible, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG487.4 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG491.1 ft. MGO - General Observation - MAG COAT 80% FINISH491.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE491.8 ft. AMH - Downstream Manhole, Survey Ends - 5:50AM

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • General Observation - MAG COAT 80% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 80% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - SWOLLEN BLISTERING CONCRETE

    165.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - SWOLLEN BLISTERING CONCRETE

  • Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    394.6 ft. - Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    428 ft. - Surface Aggregate Visible, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    487.4 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (12)

DistanceCodeObservation
487.4SAVSEVERE AGG
491.1MGOMAG COAT 80% FINISH
491.1SSSBLISTERING CONCRETE
0MWL
394.6SAPSEVERE AGG
2SSSBLISTERING CONCRETE
491.8AMH5:50AM
165.3SSSSWOLLEN BLISTERING CONCRETE
2MGOMAG COAT 80% START 8:00 TO 4:00
428SAVSEVERE AGG
0AMH5:05AM
0MWM

Properties (6)

custom_field_three
SPORATIC SEVERE AGG-80% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2018-01-16T02:46:33-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false