Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 16, 2018, 10:44 AM
  • Section#5_H 0113_H 0112__1162018__G6919.mp4

Date
01/16/2018
W/O
0683963
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00165
PipeID
P10564
Time
2:44 AM
Certificate
U-101406022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6919
Sewer Name
H JOINT OUTFALL H - UNIT 1F
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20180113MDM_JOINT_OUTFALL_H_UNIT_1F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
H 0113
Downstream MH
H 0112
Dir. of Survey
Downstream
Length Surveyed
135.9 ft.
Total Length
135.9 ft.
Structural Index
2
Structural Quick
2E00
Structural Rating
58
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
58
Pipe schematic from manhole H 0113 to H 0112
MH: H 0113MH: H 0112downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE2 ft. MGO - General Observation - MAG COAT 90% START 8:00 TO 4:0053.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE133.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE135.6 ft. MGO - General Observation - 90% MAG COAT FINISH135.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE135.9 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • General Observation - MAG COAT 90% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 90% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    53.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    133.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

Observations (10)

DistanceCodeObservation
2SSSBLISTERING CONCRETE
0MWL
0AMH4:45AM
53.3SSSBLISTERING CONCRETE
135.6MGO90% MAG COAT FINISH
135.6SSSBLISTERING CONCRETE
135.9AMH5:00AM
2MGOMAG COAT 90% START 8:00 TO 4:00
133.6SSSBLISTERING CONCRETE
0MWM

Properties (6)

custom_field_three
BLISTERING CONCRETE -90% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2018-01-16T02:44:35-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false