Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2019, 11:15 AM
  • 02 1032_02 1031_642019_043558.mp4

Date
06/04/2019
W/O
0772204
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00280
PipeID
P03606
Time
4:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1221
Sewer Name
02 MONTEBELLO CITY TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20290604MDM_M0NTEBELLO_CITY_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1032
Downstream MH
02 1031
Dir. of Survey
Downstream
Length Surveyed
329.6 ft.
Total Length
329.6 ft.
Structural Index
3
Structural Quick
4324
Structural Rating
20
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole 02 1032 to 02 1031
MH: 02 1032MH: 02 1031downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED21.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AG23.9 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED26.2 ft. MGO - General Observation - MAG COAT 20% START32.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG40 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped40.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED47.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped93.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped96.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped143.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped145.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped148.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED194.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped197.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped220.7 ft. MGO - General Observation - 20% MAG FINISH236.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped246.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped295.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped298.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped316.3 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start329 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED329 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish329 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active329 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG329 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active329.6 ft. AMH - Downstream Manhole, Survey Ends - 5:20AM

Observation photos (8)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AG

    21.4 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AG

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    23.9 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • General Observation - MAG COAT 20% START

    26.2 ft. - General Observation - MAG COAT 20% START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    32.5 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    40.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    148.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

Observations (32)

DistanceCodeObservation
145.9TFCCapped
148.8SSSPEELING CONCRETE SEVERE AGG ATTACHED
329SSSPEELING CONCRETE SEVERE AGG ATTACHED
236.1TFCCapped
329DSGV
26.2MGOMAG COAT 20% START
0AMH4:35AM
143.3TFCCapped
197.8TFCCapped
2SAMSEVERE AGG
295.8TFCCapped
96.5TFCCapped
0MWM
329MGOConn. @ Mh, 9 O' Clock. Active
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
21.4SAMSEVERE AG
47.3TFCCapped
194.7TFCCapped
0MWL
0MGOConn. @ Mh, 9 O' Clock. Active
40TFCCapped
32.5SAMSEVERE AGG
329.6AMH5:20AM
298.6TFCCapped
93.9TFCCapped
246.5TFCCapped
329SAMSEVERE AGG
40.1SSSPEELING CONCRETE SEVERE AGG ATTACHED
316.3DSGV
23.9SSSPEELING CONCRETE SEVERE AGG ATTACHED
220.7MGO20% MAG FINISH
329MGOConn. @ Mh, 3 O' Clock. Active

Properties (6)

custom_field_three
PEELIN CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2019-06-04T04:15:57-07:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false