Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2019, 10:32 AM
  • 02 1034_02 1033_642019_033912.mp4

Date
06/04/2019
W/O
0772204
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00280
PipeID
P03608
Time
3:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1221
Sewer Name
02 MONTEBELLO CITY TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20290604MDM_M0NTEBELLO_CITY_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1034
Downstream MH
02 1033
Dir. of Survey
Downstream
Length Surveyed
329.7 ft.
Total Length
329.7 ft.
Structural Index
3
Structural Quick
4231
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 02 1034 to 02 1033
MH: 02 1034MH: 02 1033downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG5.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED36.1 ft. MGO - General Observation - 20% MAG COAT START44.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped47.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped49.6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG70.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped88.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - Capped91.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped110 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped122.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped127.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped158.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped171.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped190.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped192.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped213.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped213.3 ft. MGO - General Observation - 40% MAG COAT START242 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped262.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped264.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped318.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT329.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHD329.2 ft. MGO - General Observation - 40% MAG COAT FINISH329.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active329.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active329.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG329.7 ft. AMH - Downstream Manhole, Survey Ends - 4:05AM

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start -  PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    5.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • General Observation - 20% MAG COAT START

    36.1 ft. - General Observation - 20% MAG COAT START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    49.6 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - 40% MAG COAT START

    213.3 ft. - General Observation - 40% MAG COAT START

Observations (34)

DistanceCodeObservation
0MGOConn. @ Mh, 3 O' Clock. Active
36.1MGO20% MAG COAT START
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
329.2SSSPEELING CONCRETE SEVERE AGG ATTACHD
192.7TFCCapped
49.6SAMSEVERE AGG
213.3TFCCapped
262.5TFCCapped
190.4TFCCapped
329.2MGO40% MAG COAT FINISH
242TFCCapped
127.4TFCCapped
5.3SSSPEELING CONCRETE SEVERE AGG ATTACHED
329.2MGOConn. @ Mh, 3 O' Clock. Active
91.8TFCCapped
318.5FLSLIGHT
0MGOConn. @ Mh, 9 O' Clock. Active
329.2MGOConn. @ Mh, 9 O' Clock. Active
0MWL
122.9TFCCapped
47.2TFCCapped
44.6TFCCapped
329.7AMH4:05AM
110TFCCapped
213.3MGO40% MAG COAT START
329.2SAMSEVERE AGG
158.9TFCCapped
0AMH3:35AM
0MWM
70.7TFCCapped
264.8TFCCapped
88.9TFCCapped
2SAMSEVERE AGG
171.7TFCCapped

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2019-06-04T03:32:52-07:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false