Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 28, 2019, 08:26 AM
  • 03 0469_03 0468 _03282019_013247.mp4

Date
03/28/2019
W/O
755907
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00387
PipeID
P04798
Time
1:26 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6503
Sewer Name
03 NORTH LONG BEACH TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Routine Assessment
Project
WO_755907_TV03025_MAR2019
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
03 0469
Downstream MH
03 0468
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 03 0469 to 03 0468
MH: 03 0469MH: 03 0468downstream0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. MWM - Water Mark, 100 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 04692 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES2 ft. MGO - General Observation - VIEW OF THE SIPHON DOWNLEG FROM U/S MH2 ft. MGO - General Observation - PIPE APPEARS REPAIRED2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES2 ft. MGO - General Observation - CIPP LINER

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
2DAGS
2MGOVIEW OF THE SIPHON DOWNLEG FROM U/S MH
2MGOPIPE APPEARS REPAIRED
2SAP
2SRV
2MGOCIPP LINER
0MWL
0MWM
0AMH03 0469

Properties (6)

custom_field_two
1
customer
LACSD
datetime
2019-03-28T01:26:29-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
36115