Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2018, 06:23 AM
  • 29 0559_29 0516 _20062018_234007.mp4

Date
06/20/2018
W/O
706888
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01106
PipeID
P24588
Time
11:23 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5740
Sewer Name
29 19TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
WO_706888_TV29054_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0516
Downstream MH
29 0559
Dir. of Survey
Upstream
Length Surveyed
260.1 ft.
Total Length
260.1 ft.
Structural Index
3
Structural Quick
3F11
Structural Rating
103
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
103
Pipe schematic from manhole 29 0516 to 29 0559
MH: 29 0516MH: 29 0559upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 05591.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"45.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"50.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.8 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"144.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"156.6 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"164 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start192 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES210.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES217.5 ft. JSM - Joint Separated Medium260.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE260.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK260.1 ft. MWM - Water Mark, 5 %of cross sectional area260.1 ft. AMH - Downstream Manhole, Survey Begins - 29 0516260.1 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (4)

  • Joint Separated Medium

    42.6 ft. - Joint Separated Medium

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    49.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    68.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    96.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
96.1CM
258.6CM
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
49.8CM
0MWM
42.6JSM
103.5TFA
0AMH29 0516
0MWL
188.3TBA
115.4TFA
260.1AMH29 0559
258.1TFC
215TFA
68.1CM
209.6TF

Properties (6)

additional_info
SC359706
custom_field_two
3
customer
LACSD
datetime
2018-06-20T23:23:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false