Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2019, 04:17 AM
  • 18 1121_18 1120 _03202019_215303.mp4

Date
03/20/2019
W/O
756123
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00711
PipeID
P14974
Time
9:17 PM
Certificate
U-715-7000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6487
Sewer Name
18 STAGE ROAD JUNCTION TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_756123_TV18190_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
18 1121
Downstream MH
18 1120
Dir. of Survey
Downstream
Length Surveyed
268.8 ft.
Total Length
268.8 ft.
Structural Index
4
Structural Quick
4G31
Structural Rating
159
O&M Index
2
O&M Quick
312G
O&M Rating
85
Overall Index
3
Overall Quick
Overall Rating
244
Pipe schematic from manhole 18 1121 to 18 1120
MH: 18 1121MH: 18 1120downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 11210 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area1.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES6.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES14.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"15.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"49.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish61.7 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES62.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start69.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"82.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start114.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"117.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"172.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"221.1 ft. RMC - Roots Medium Connection, from 04 to 08 o'clock, 15 %, within 8 inches of joint: YES221.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"234.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish247.3 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES265.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish268.8 ft. MGO - General Observation - CONNECTION IN MH 9 OCLOCK268.8 ft. AMH - Downstream Manhole, Survey Ends - 18 1120

Observation photos (8)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    1.8 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    61.7 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    62.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    82.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 04 to 08 o'clock, 15 %, within 8 inches of joint: YES

    221.1 ft. - Roots Medium Connection, from 04 to 08 o'clock, 15 %, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    247.3 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
221.1RMC
0AMH18 1121
234.6FM
49.4FM
265.9DAGS
62.8DAGS
20TFC
114.9TBA
117.6TFC
221.1TFC
268.8MGOCONNECTION IN MH 9 OCLOCK
82.9FM
6.7FM
247.3CL
0MWL
268.8AMH18 1120
0MWM
15.9FM
14.6TBA
69.2TFC
172.4TFC
61.7CM
1.8CL

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-20T21:17:15-07:00
documentation
PROPIPE
is_lateral_inspection
false