Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2019, 05:58 AM
  • 18 1097_18 1153 _03202019_232904.mp4

Date
03/20/2019
W/O
756105
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00699
PipeID
P14263
Time
10:58 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6488
Sewer Name
18 SANTA FE STREET RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_756105_TV18189_MAR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 1097
Downstream MH
18 1153
Dir. of Survey
Downstream
Length Surveyed
670.4 ft.
Total Length
670.4 ft.
Structural Index
3
Structural Quick
3Y00
Structural Rating
393
O&M Index
3
O&M Quick
4312
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
407
Pipe schematic from manhole 18 1097 to 18 1153
MH: 18 1097MH: 18 1153downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 10970 ft. MGO - General Observation - MULTIPLE CONNECTIONS IN MH0 ft. MWL - Water Level, 50 %of cross sectional area10.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start38.7 ft. LR - Alignment Right, 5 %127.9 ft. IR - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES255.3 ft. IR - Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES658.5 ft. LR - Alignment Right, 5 %666.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish670.4 ft. AMH - Downstream Manhole, Survey Ends - 18 1153

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

    127.9 ft. - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES

    255.3 ft. - Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MWM
0AMH18 1097
0MGOMULTIPLE CONNECTIONS IN MH
658.5LR
255.3IR
127.9IR
666.3SAP
10.1SAP
670.4AMH18 1153
38.7LR
0MWL

Properties (6)

custom_field_two
2
customer
LACSD
datetime
2019-03-20T22:58:05-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26802