Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2019, 09:27 AM
  • 18 0374_18 0373 _03182019_024458.mp4

Date
03/18/2019
W/O
755597
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00690
PipeID
P14208
Time
2:27 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6478
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_755957_TV18095_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0374
Downstream MH
18 0373
Dir. of Survey
Downstream
Length Surveyed
325.9 ft.
Total Length
325.9 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0374 to 18 0373
MH: 18 0374MH: 18 0373downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03740 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED4.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start92 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"206.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"316.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"322.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0373325.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
4.8FM
0MWM
206.7TFC
316.9TFA
322.6FM
325.9AMH18 0373
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
325.9MGOCONNECTION AT MH 9 O'CLOCK
0MWL
92TFA
0AMH18 0374
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-18T02:27:18-07:00
documentation
PROPIPE
is_lateral_inspection
false