Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2019, 08:00 AM
  • 18 0379_18 0378 _03182019_012232.mp4

Date
03/18/2019
W/O
755597
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00690
PipeID
P14213
Time
1:00 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6478
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_755957_TV18095_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0379
Downstream MH
18 0378
Dir. of Survey
Downstream
Length Surveyed
350.4 ft.
Total Length
350.4 ft.
Structural Index
4
Structural Quick
4300
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
12
Pipe schematic from manhole 18 0379 to 18 0378
MH: 18 0379MH: 18 0378downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03796 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES9 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES12.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"88.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"181.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"289.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"342.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"348.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0378

Observation photos (3)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    9 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
9FM
0MGOCONNECTION AT MH 3 O'CLOCK
0MWL
0MWM
348.9FM
12.6FM
0AMH18 0379
19.1TFC
181.8TFC
350.4AMH18 0378
342.4TFC
88.1TFC
6FM
289.4TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-18T01:00:13-07:00
documentation
PROPIPE
is_lateral_inspection
false