21 1031_21 1030 _03262019_025600.mp4
2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start
30.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES
142.3 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES
144.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES
180.2 ft. - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES
191.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start
194.5 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR
194.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES
| Distance | Code | Observation |
|---|---|---|
| 216.6 | TFC | — |
| 166.2 | TFC | — |
| 194.5 | RFJ | — |
| 316.3 | TFC | — |
| 142.3 | CM | — |
| 143.1 | TFC | — |
| 335.8 | AMH | 21 1030 |
| 194.9 | FM | — |
| 0 | AMH | 21 1031 |
| 334.1 | CM | — |
| 115.8 | TFC | — |
| 0 | MGO | CAPPED CONNECTION AT 9 O' CLOCK AT |
| 144.7 | CM | — |
| 2.2 | DAGS | — |
| 0 | MWM | — |
| 189.4 | TFC | — |
| 247.5 | TFC | — |
| 30.6 | CL | — |
| 180.2 | FS | — |
| 334.1 | DAGS | — |
| 191.2 | CM | — |
| 293.4 | TFC | — |
| 266.3 | TFC | — |
| 0 | MWL | — |
| 64.2 | TFC | — |