Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2019, 07:38 AM
  • 22 0298_22 0297_02042019_235742.mp4

Date
02/04/2019
W/O
745519
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00793
PipeID
P16584
Time
11:38 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6381
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_745519_TV22014_JAN2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0297
Downstream MH
22 0298
Dir. of Survey
Upstream
Length Surveyed
431.6 ft.
Total Length
431.6 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 22 0297 to 22 0298
MH: 22 0297MH: 22 0298upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 02982.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. SSS - Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Finish47.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"180 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"239.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"272.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"308.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"328.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"361.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"393.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"421.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"429.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start429.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start429.6 ft. SSS - Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Start431.6 ft. AMH - Downstream Manhole, Survey Begins - 22 0297431.6 ft. MWM - Water Mark, 25 %of cross sectional area431.6 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
2SAP
429.5DAGS
251.6TFA
308.1TFC
383.7TFA
431.6AMH22 0298
429.5SAP
159.1TFA
0AMH22 0297
70.1TFA
2DAGS
0MWM
103.4TFC
192.2TFA
303.2TFA
9.9TFA
123.2TFA
37.9TFC
0MWL
233.7TFA
429.5SSS
2SSS

Properties (6)

additional_info
SC365693
custom_field_two
2
customer
LACSD
datetime
2019-02-04T23:38:41-08:00
documentation
PRO PIPE
is_lateral_inspection
false