Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2019, 06:08 AM
  • 29 0083_29 0082 _01092019_223115.mp4

Date
01/09/2019
W/O
740318
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00265
PipeID
P23863
Time
10:08 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5333
Sewer Name
29 33RD STREET TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_740318_TV29110_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0083
Downstream MH
29 0082
Dir. of Survey
Downstream
Length Surveyed
321.3 ft.
Total Length
321.3 ft.
Structural Index
3
Structural Quick
4232
Structural Rating
16
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 29 0083 to 29 0082
MH: 29 0083MH: 29 0082downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 00830 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWM - Water Mark, 35 %of cross sectional area6.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6.3 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES9.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES12 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"18.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"40.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES47 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish47 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start285.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"287.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"318.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish321.2 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH321.3 ft. AMH - Downstream Manhole, Survey Ends - 29 0082

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    6.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    6.3 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    9.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    40.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    47 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
6.3DAGS
47CM
0AMH29 0083
318.6FM
47FM
321.2MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
321.3AMH29 0082
18.4TF
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
9.2CM
285.4TF
318.6DAGS
0MWL
6.3CL
40.5FM
287.1TF
12CM
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
16.2TF
0MWM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-01-09T22:08:22-08:00
documentation
PROPIPE
is_lateral_inspection
false