Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2019, 05:34 AM
  • 29 0085_29 0084 _01092019_215733.mp4

Date
01/09/2019
W/O
740318
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00265
PipeID
P23865
Time
9:34 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5333
Sewer Name
29 33RD STREET TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_740318_TV29110_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0085
Downstream MH
29 0084
Dir. of Survey
Downstream
Length Surveyed
323.1 ft.
Total Length
323.1 ft.
Structural Index
4
Structural Quick
5242
Structural Rating
21
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
23
Pipe schematic from manhole 29 0085 to 29 0084
MH: 29 0085MH: 29 0084downstream0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 29 00850 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWL - Water Level, 20 %of cross sectional area6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES7.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES18 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"21.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"69.3 ft. B - Broken, from 11 to 05 o'clock, within 8 inches of joint: YES72.3 ft. B - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES304.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"306.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"320.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish323 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH323.1 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH323.1 ft. AMH - Downstream Manhole, Survey Ends - 29 0084

Observation photos (6)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    12.4 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 11 to 05 o'clock, within 8 inches of joint: YES

    69.3 ft. - Broken, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

    72.3 ft. - Broken, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
12.4FL
320.3FM
6FM
304.6TF
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
19.3TF
0AMH29 0085
7.8DAGS
18FM
0MWM
323.1MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
69.3B
21.6TF
323MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
306.9TF
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
320.3DAGS
0MWL
72.3B
323.1AMH29 0084

Properties (5)

custom_field_two
1
customer
LACSD
datetime
2019-01-09T21:34:57-08:00
documentation
PROPIPE
is_lateral_inspection
false