Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2019, 08:27 AM
  • F 0277_F 0096 _01092019_003728.mp4

Date
01/09/2019
W/O
740022
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00039
PipeID
P10212
Time
12:27 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6317
Sewer Name
F JOINT OUTFALL F - UNIT 4
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
RFIR_WO_740022_TV02205_DEC2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
F 0277
Downstream MH
F 0096
Dir. of Survey
Downstream
Length Surveyed
297.9 ft.
Total Length
297.9 ft.
Structural Index
4
Structural Quick
5K3K
Structural Rating
472
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
472
Pipe schematic from manhole F 0277 to F 0096
MH: F 0277MH: F 0096downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 02770 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area3.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start297.9 ft. AMH - Downstream Manhole, Survey Ends - F 0096297.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish297.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
3.4SRV
0MWL
297.9AMHF 0096
0AMHF 0277
3.4SAP
0MGOCONNECTION AT MH 9 O'CLOCK
297.9SAP
297.9SRV
0MWM

Properties (6)

additional_info
SC365751
custom_field_two
1
customer
LACSD
datetime
2019-01-09T00:27:21-08:00
documentation
PROPIPE
is_lateral_inspection
false