Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2019, 08:15 AM
  • 01 1126_01 1125_03072019_013638.mp4

Date
03/07/2019
W/O
750757
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00210
PipeID
P01978
Time
12:15 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6464
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_750757_TV01246_FEB2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1126
Downstream MH
01 1125
Dir. of Survey
Downstream
Length Surveyed
283.1 ft.
Total Length
283.1 ft.
Structural Index
3
Structural Quick
5134
Structural Rating
21
O&M Index
2
O&M Quick
3221
O&M Rating
11
Overall Index
2
Overall Quick
Overall Rating
32
Pipe schematic from manhole 01 1126 to 01 1125
MH: 01 1126MH: 01 1125downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11260 ft. MWL - Water Level, 5 %of cross sectional area4.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES21.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"27.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES30.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start30.5 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES32.8 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES35.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES48.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start63.2 ft. RML - Roots Medium Lateral, from 03 to 09 o'clock, 35 %, within 8 inches of joint: YES63.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"68 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"107 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"114.6 ft. RFL - Roots Fine Lateral, at 08 o'clock114.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"145 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 8"145 ft. HSV - Hole Soil Visible, at 01 o'clock, within 8 inches of joint: YES - AT BREAK IN LATERAL151.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"176.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"197.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"220.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"220.8 ft. RFL - Roots Fine Lateral, at 08 o'clock243.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"248.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"248.9 ft. RFL - Roots Fine Lateral, at 04 o'clock280.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish280.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish283.1 ft. AMH - Downstream Manhole, Survey Ends - 01 1125

Observation photos (12)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    4.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    27.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    30.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    30.5 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    32.8 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    35.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    48.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 03 to 09 o'clock, 35 %, within 8 inches of joint: YES

    63.2 ft. - Roots Medium Lateral, from 03 to 09 o'clock, 35 %, within 8 inches of joint: YES

  • Roots Fine Lateral, at 08 o'clock

    114.6 ft. - Roots Fine Lateral, at 08 o'clock

  • Hole Soil Visible, at 01 o'clock, within 8 inches of joint: YES - AT BREAK IN LATERAL

    145 ft. - Hole Soil Visible, at 01 o'clock, within 8 inches of joint: YES - AT BREAK IN LATERAL

  • Roots Fine Lateral, at 08 o'clock

    220.8 ft. - Roots Fine Lateral, at 08 o'clock

  • Roots Fine Lateral, at 04 o'clock

    248.9 ft. - Roots Fine Lateral, at 04 o'clock

Observations (30)

DistanceCodeObservation
114.6RFL
4.4CL
32.8CM
27.5CM
48.4CM
176.8TFA
248.9TFA
220.8TFA
280.2CM
30.5DAGS
0MWM
145TBD
0AMH01 1126
63.2RML
197.3TFA
248.9RFL
280.2DAGS
68TFA
107TFA
243.7TFA
283.1AMH01 1125
145HSVAT BREAK IN LATERAL
21.4TFA
151.1TF
35.4CL
220.8RFL
30.5CM
63.2TFA
0MWL
114.6TFA

Properties (5)

custom_field_two
1
customer
LACSD
datetime
2019-03-07T00:15:59-08:00
documentation
PROPIPE
is_lateral_inspection
false