Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 30, 2019, 09:26 AM
  • 18 0456_18 0455 _01302019_014911.mpg

Date
01/30/2019
W/O
745744
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00691
PipeID
P14308
Time
1:26 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6373
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_745744_TV18140_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0456
Downstream MH
18 0455
Dir. of Survey
Downstream
Length Surveyed
470.2 ft.
Total Length
470.2 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
276
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
280
Pipe schematic from manhole 18 0456 to 18 0455
MH: 18 0456MH: 18 0455downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04560 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area6.1 ft. MGO - General Observation - MAG COAT6.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start225.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"270.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"420.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"466.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish466.3 ft. MMC - Material Change, Vitrified clay pipe467.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"470.2 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK470.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0455

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH18 0456
470.2MGOCONNECTION AT MH 9 OCLOCK
420.8TFA
466.3SAP
270.3TFA
466.3MMC
6.1MGOMAG COAT
0MWL
0MWM
467.8TF
225.6TFA
470.2AMH18 0455
6.2SAP

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-01-30T01:26:05-08:00
documentation
PROPIPE
is_lateral_inspection
false