Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2019, 01:10 PM
  • 05 0660_05 0659 _01282019_052844.mpg

Date
01/28/2019
W/O
745405
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00520
PipeID
P05885
Time
5:10 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5353
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_745405_TV05343_JAN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 0659
Downstream MH
05 0660
Dir. of Survey
Upstream
Length Surveyed
312.2 ft.
Total Length
312.2 ft.
Structural Index
3
Structural Quick
413D
Structural Rating
73
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
213
Pipe schematic from manhole 05 0659 to 05 0660
MH: 05 0659MH: 05 0660upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 06600 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES2.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish43.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"93 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"101.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start113.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES141.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"156 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - UNKNOWN156.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES191.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"196.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start286 ft. H - Hole, at 01 o'clock, within 8 inches of joint: YES312.2 ft. MWL - Water Level, 20 %of cross sectional area312.2 ft. AMH - Downstream Manhole, Survey Begins - 05 0659312.2 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (1)

  • Hole, at 01 o'clock, within 8 inches of joint: YES

    26.2 ft. - Hole, at 01 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
26.2H
198.4CM
116DAGS
210.8CM
309.6FM
0MWL
312.2DAGS
170.8TFA
268.7TFA
312.2AMH05 0660
312.2DSZ
309.6CM
0AMH05 0659
156.2DSZUNKNOWN
121.1TFA
0MWM
219.2TFA
156CM

Properties (5)

custom_field_two
1
customer
LACSD
datetime
2019-01-28T05:10:24-08:00
documentation
PROPIPE
is_lateral_inspection
false