Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2019, 07:55 AM
  • 01 0205_01 0204_01082019_000450.mp4

Date
01/07/2019
W/O
740026
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00202
PipeID
P01247
Time
11:55 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5331
Sewer Name
01 COMPTON AVENUE TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_740026_TV01237_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0205
Downstream MH
01 0204
Dir. of Survey
Downstream
Length Surveyed
181.6 ft.
Total Length
181.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 01 0205 to 01 0204
MH: 01 0205MH: 01 0204downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02050 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 45 %of cross sectional area6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start66.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"121.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"176.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"180.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish181.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0204

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMH01 0205
176.3TFA
0MWM
181.6AMH01 0204
121.6TFA
180.8CM
0MWL
66.9TF
6CM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-01-07T23:55:13-08:00
documentation
PROPIPE
is_lateral_inspection
false