Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2019, 09:38 AM
  • 01 0194_01 0193_01082019_015452.mp4

Date
01/08/2019
W/O
740026
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00202
PipeID
P01236
Time
1:38 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5331
Sewer Name
01 COMPTON AVENUE TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_740026_TV01237_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0194
Downstream MH
01 0193
Dir. of Survey
Downstream
Length Surveyed
272 ft.
Total Length
272 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 0194 to 01 0193
MH: 01 0194MH: 01 0193downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 01940 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0.1 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH4.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start12.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"17.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"41.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"59.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"80.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"86.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 8" - ROOTS AT CONNECTION101.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"104.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"112.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"135.5 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8" - ROOTS AT CONNECTION155 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"160.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"212.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"221 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"230 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES250.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"259.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"268.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish272 ft. AMH - Downstream Manhole, Survey Ends - 01 0193272 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    230 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
17.5TB
12.4TFC
104.3TFA
268.8CM
4.9CM
80.7TFC
259.6TF
0AMH01 0194
272AMH01 0193
155TFC
41.9TFC
0.1MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
230FL
0MWL
221TF
212.2TFC
86.6TBAROOTS AT CONNECTION
0MWM
101.5TF
112.6TBA
160.8TFA
272MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
250.7TF
135.5TBAROOTS AT CONNECTION
59.6TFA

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-01-08T01:38:47-08:00
documentation
PROPIPE
is_lateral_inspection
false