Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2019, 06:13 AM
  • 01 0202_01 0201_01072019_222840.mp4

Date
01/07/2019
W/O
740026
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00202
PipeID
P01244
Time
10:13 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5331
Sewer Name
01 COMPTON AVENUE TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_740026_TV01237_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0202
Downstream MH
01 0201
Dir. of Survey
Downstream
Length Surveyed
313.1 ft.
Total Length
313.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 01 0202 to 01 0201
MH: 01 0202MH: 01 0201downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02026.9 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES8.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"18.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start39.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start50 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"58.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"99.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"108.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"116.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"160.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"199.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"207.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"254.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"257.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"305 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"307.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"311.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish311.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish313.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0201

Observation photos (3)

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    6.9 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    39.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
307.4TFA
207.6TFA
0MWL
0MWM
311.2CM
313.1AMH01 0201
8.5TFA
199.3TFA
108.1TFA
257.7TFA
311.2DAGS
99.5TFA
116.5TFA
6.9CL
0AMH01 0202
254.9TFA
305TFA
58.3TFA
39.5DAGS
50TF
18.6CM
160.7TFA

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-01-07T22:13:59-08:00
documentation
PROPIPE
is_lateral_inspection
false