Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2019, 06:08 AM
  • 01 0182_01 0181_01082019_222740.mp4

Date
01/08/2019
W/O
740026
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00202
PipeID
P01222
Time
10:08 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5332
Sewer Name
01 COMPTON AVENUE TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_740026_TV01237_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Square
Height
15 in.
Width
15 in.
Upstream MH
01 0182
Downstream MH
01 0181
Dir. of Survey
Downstream
Length Surveyed
329.2 ft.
Total Length
329.2 ft.
Structural Index
3
Structural Quick
3400
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0182 to 01 0181
MH: 01 0182MH: 01 0181downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 01820 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH1.6 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH6.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start35.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"59.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"62.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"82.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"85.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"92.3 ft. FS - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES94.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"108.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"138.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"214.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"217.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"241.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"243.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"253.8 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES261.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"264.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"286.6 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES288 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"290.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"317.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"320.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"326.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish329.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0181329.2 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH329.2 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (4)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    92.3 ft. - Fracture Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    253.8 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    286.6 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (31)

DistanceCodeObservation
317.5TFC
253.8FS
108.6TF
326.4CM
0MWM
35.6TFC
94.1TFC
62.3TFC
329.2AMH01 0181
264.1TF
320.2TFA
82.6TFC
286.6FS
329.2MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
1.6MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
243.7TFC
290.8TFC
0MWL
329.2MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
241.1TFA
0AMH01 0182
6.4CM
261.7TFC
288TFC
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
92.3FS
59.1TFC
138.4TFC
217.2TF
85.4TF
214.3TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-01-08T22:08:26-08:00
documentation
PROPIPE
is_lateral_inspection
false