Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2019, 10:16 AM
  • 01 0191A_01 0191_01082019_022810.mp4

Date
01/08/2019
W/O
740026
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00202
PipeID
P01233
Time
2:16 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5331
Sewer Name
01 COMPTON AVENUE TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_740026_TV01237_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0191A
Downstream MH
01 0191
Dir. of Survey
Downstream
Length Surveyed
149.9 ft.
Total Length
149.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 01 0191A to 01 0191
MH: 01 0191AMH: 01 0191downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 0191A0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH2.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start13.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"25.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"28 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"73.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"75.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"99.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"126.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"147.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish149.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0191149.9 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observations (15)

DistanceCodeObservation
0AMH01 0191A
73.1TFC
0MWL
25.2TF
13.4TFC
149.9AMH01 0191
0MWM
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
99.5TFC
149.9MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
2.6CM
147.1CM
28TFC
126.5TFC
75.3TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-01-08T02:16:39-08:00
documentation
PROPIPE
is_lateral_inspection
false