Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2019, 06:46 AM
  • 02 2242_02 0990 _04292019_235725.mp4

Date
04/29/2019
W/O
761346
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00279
PipeID
P03562
Time
11:46 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6522
Sewer Name
02 MONTEBELLO TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_761346_TV02334_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0990
Downstream MH
02 2242
Dir. of Survey
Upstream
Length Surveyed
219 ft.
Total Length
219 ft.
Structural Index
4
Structural Quick
4G00
Structural Rating
164
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
164
Pipe schematic from manhole 02 0990 to 02 2242
MH: 02 0990MH: 02 2242upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 22421.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish50 ft. RPZ - Repair Other, within 8 inches of joint: YES - TOP HALF OF PIPE REPLACED209.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start218.9 ft. MWM - Water Mark, 45 %of cross sectional area219 ft. AMH - Downstream Manhole, Survey Begins - 02 0990219 ft. MWL - Water Level, 40 %of cross sectional area219 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK

Observation photos (2)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES - TOP HALF OF PIPE REPLACED

    169 ft. - Repair Other, within 8 inches of joint: YES - TOP HALF OF PIPE REPLACED

Observations (8)

DistanceCodeObservation
217.2FM
219AMH02 2242
9.8FM
0.1MWM
0AMH02 0990
0MWL
0MGOCONNECTION IN MH 3 OCLOCK
169RPZTOP HALF OF PIPE REPLACED

Properties (4)

custom_field_two
2
customer
LACSD
datetime
2019-04-29T23:46:17-07:00
is_lateral_inspection
false