Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2019, 09:28 AM
  • 14 0539_14 0538 _03182019_025722.mp4

Date
03/18/2019
W/O
750675
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18630
Time
2:28 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6428
Sewer Name
14 35TH STREET WEST TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_750675_TV14074_FEB2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
14 0539
Downstream MH
14 0538
Dir. of Survey
Downstream
Length Surveyed
526.4 ft.
Total Length
526.4 ft.
Structural Index
3
Structural Quick
3T00
Structural Rating
315
O&M Index
2
O&M Quick
2T00
O&M Rating
210
Overall Index
3
Overall Quick
Overall Rating
525
Pipe schematic from manhole 14 0539 to 14 0538
MH: 14 0539MH: 14 0538downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 05390 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start526.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish526.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish526.4 ft. AMH - Downstream Manhole, Survey Ends - 14 0538

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
0AMH14 0539
526.4DAGS
526.4SAP
526.4AMH14 0538
2SAP
2DAGS
0MWL

Properties (5)

additional_info
SC365946
custom_field_two
2
customer
LACSD
datetime
2019-03-18T02:28:48-07:00
is_lateral_inspection
false