Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 20, 2019, 09:11 AM
  • 01 1355_01 0799_02202019_013830.mp4

Date
02/20/2019
W/O
750661
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00197
PipeID
P01503
Time
1:11 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6279
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_750661_TV01264_FEB2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0799
Downstream MH
01 1355
Dir. of Survey
Upstream
Length Surveyed
327.7 ft.
Total Length
327.7 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
14
Pipe schematic from manhole 01 0799 to 01 1355
MH: 01 0799MH: 01 1355upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 13550 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish52.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"66.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"75.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"96.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"116.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"123.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"151.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"164.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"175 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"198 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"208.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"218.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"245.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"258.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"288.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"293.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish293.7 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Start297.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"323.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start327.7 ft. MWM - Water Mark, 75 %of cross sectional area327.7 ft. AMH - Downstream Manhole, Survey Begins - 01 0799327.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK327.7 ft. MWL - Water Level, 45 %of cross sectional area

Observation photos (2)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    34 ft. - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
0MWM
4.1FM
29.9TFC
69.4TFC
118.9TFC
34FM
38.9TFC
0AMH01 0799
261.2TFC
163.5TFA
0MGOCONNECTION AT MH 9 O'CLOCK
275.4TFC
152.7TFC
231.3TFC
0MWL
34B
251.9TFC
211.2TFC
82.5TFC
327.7AMH01 1355
327.7B
109.4TFC
129.7TFC
176.2TFC
204.3TFC

Properties (4)

custom_field_two
1
customer
LACSD
datetime
2019-02-20T01:11:09-08:00
is_lateral_inspection
false