Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 20, 2019, 10:51 AM
  • 01 0794_01 0793_02202019_031352.mp4

Date
02/20/2019
W/O
750661
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00197
PipeID
P01496
Time
2:51 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6279
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_750661_TV01264_FEB2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0794
Downstream MH
01 0793
Dir. of Survey
Downstream
Length Surveyed
294.9 ft.
Total Length
294.9 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 01 0794 to 01 0793
MH: 01 0794MH: 01 0793downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 07940 ft. MWM - Water Mark, 60 %of cross sectional area2.4 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start8.5 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Start8.5 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish14.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"68.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"77.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"114 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"134.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"164.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"183 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"216.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"234.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"267.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"285.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"292.2 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish292.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish294.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK294.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0793

Observation photos (1)

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
0MWL
216.5TFC
234.2TFC
294.9MGOCONNECTION AT MH 9 O'CLOCK
294.9AMH01 0793
0MGOCONNECTION AT MH 3 O'CLOCK
0AMH01 0794
285.3TFC
0MWM
8.5B
164.2TFC
2.4FM
77.6TFC
14.3TFC
267.7TFC
68.1TFC
292.2B
2.4DAGS
114TFC
183TFC
292.2DAGS
8.5FM
134.9TFC

Properties (4)

custom_field_two
1
customer
LACSD
datetime
2019-02-20T02:51:25-08:00
is_lateral_inspection
false