Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 20, 2019, 10:12 AM
  • 01 1369_01 0795_02202019_023113.mp4

Date
02/20/2019
W/O
750661
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00197
PipeID
P01498
Time
2:12 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6279
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_750661_TV01264_FEB2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1369
Downstream MH
01 0795
Dir. of Survey
Downstream
Length Surveyed
135.5 ft.
Total Length
135.5 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
2
O&M Quick
4121
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 01 1369 to 01 0795
MH: 01 1369MH: 01 0795downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13690 ft. MWL - Water Level, 30 %of cross sectional area1 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start6.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish6.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES8.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"9 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start57.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"81.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"94.4 ft. RFJ - Roots Fine Joint, from 11 to 01 o'clock, within 8 inches of joint: YES108.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"112.8 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES129.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"132.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish135.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish135.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0795

Observation photos (4)

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    1 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    6.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
57.1TF
112.8RFJ
81.2TFC
135.5DAGS
8.4TFC
6.8FM
0MWM
108.6TFC
94.4RFJ
1FM
0AMH01 1369
0MWL
9FM
1DAGS
6.8FL
132.8FM
129.5TFC
135.5AMH01 0795

Properties (4)

custom_field_two
2
customer
LACSD
datetime
2019-02-20T02:12:15-08:00
is_lateral_inspection
false