Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2019, 06:08 AM
  • 01 0056_01 0055_04102019_233716.mp4

Date
04/10/2019
W/O
761341
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00209
PipeID
P00725
Time
11:08 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5926
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_761341_TV01254_APR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0056
Downstream MH
01 0055
Dir. of Survey
Downstream
Length Surveyed
354.2 ft.
Total Length
354.2 ft.
Structural Index
4
Structural Quick
4232
Structural Rating
14
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 01 0056 to 01 0055
MH: 01 0056MH: 01 0055downstream0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00562 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start33 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"80.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"127 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"130.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"133.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"179 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"181.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"194.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish194.6 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES205 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES211.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start228.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"230.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"280 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"282.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"332.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"335.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"349.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish353.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK353.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED354.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0055

Observation photos (9)

  • General Observation - CONNECTION AT MH 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH 3 O'CLOCK

  • General Observation - CONNECTION AT MH 9 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    33 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

    194.6 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    205 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    211.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - CONNECTION AT MH 3 O'CLOCK

    353.8 ft. - General Observation - CONNECTION AT MH 3 O'CLOCK

  • General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

    353.8 ft. - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

Observations (29)

DistanceCodeObservation
0MWL
228.1TFC
351.7DAGS
354.2AMH01 0055
0MGOCONNECTION AT MH 3 O'CLOCK
282.8TF
332.6TFC
280TFC
230.9TFC
0MGOCONNECTION AT MH 9 O'CLOCK
194.6FM
181.7TFC
80.8TFC
194.6FS
211.1FM
127TB
133.1TFC
77.8TFC
349.7FM
2DAGS
353.8MGOCONNECTION AT MH 3 O'CLOCK
0MWM
130.3TFC
0AMH01 0056
179TFC
33FM
353.8MGOCONNECTION AT MH 9 O'CLOCK CAPPED
205FS
335.5TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-04-10T23:08:52-07:00
documentation
PROPIPE
is_lateral_inspection
false