Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2019, 09:00 AM
  • 03 0195_03 0194 _03122019_021439.mp4

Date
03/12/2019
W/O
756072
Weather
Light Rain
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00387
PipeID
P04795
Time
2:00 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5824
Sewer Name
03 NORTH LONG BEACH TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
14
Purpose
Routine Assessment
Project
WO_756072_TV03028_MAR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
03 0195
Downstream MH
03 0194
Dir. of Survey
Downstream
Length Surveyed
485.1 ft.
Total Length
485.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 03 0195 to 03 0194
MH: 03 0195MH: 03 0194downstream0 ft. AMH - Upstream Manhole, Survey Begins - 03 01950 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area4.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4.5 ft. MGO - General Observation - LINER421.2 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start484 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish484 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish485.1 ft. AMH - Downstream Manhole, Survey Ends - 03 0194

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
484DSC
484DAGS
421.2DSC
4.5DAGS
485.1AMH03 0194
0AMH03 0195
0MWM
4.5MGOLINER
0MWL

Properties (8)

additional_info
SC366054
custom_field_two
4
customer
LACSD
datetime
2019-03-12T02:00:04-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
FR POLY LINE
year_laid
36115