Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2019, 05:28 AM
  • 22 0503_22 0502 _04292019_224940.mp4

Date
04/29/2019
W/O
761413
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00800
PipeID
P16842
Time
10:28 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6514
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_761413_TV21156_APR2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
22 0502
Downstream MH
22 0503
Dir. of Survey
Upstream
Length Surveyed
326.5 ft.
Total Length
326.5 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
200
Pipe schematic from manhole 22 0502 to 22 0503
MH: 22 0502MH: 22 0503upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 0503, DAMAGED PIPE U/S OF 22 0503.0.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK1.6 ft. OBM - Obstacles Pipe Material, 40 %of cross sectional area, from 04 to 10 o'clock1.6 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish41.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"44.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"89.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"92.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"239.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"242.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"290 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"293.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"324.5 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start326.5 ft. AMH - Downstream Manhole, Survey Begins - 22 0502326.5 ft. MWL - Water Level, 5 %of cross sectional area326.5 ft. MWM - Water Mark, 5 %of cross sectional area326.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Obstacles Pipe Material, 40 %of cross sectional area, from 04 to 10 o'clock

    324.9 ft. - Obstacles Pipe Material, 40 %of cross sectional area, from 04 to 10 o'clock

  • Upstream Manhole, Survey Ends - 22 0503, DAMAGED PIPE U/S OF 22 0503.

    326.5 ft. - Upstream Manhole, Survey Ends - 22 0503, DAMAGED PIPE U/S OF 22 0503.

Observations (21)

DistanceCodeObservation
84TFC
285.1TFC
186TFC
281.8TFC
0AMH22 0502
0MWL
326.5AMH22 0503, DAMAGED PIPE U/S OF 22 0503.
2SAP
237.1TFC
183TFC
324.9OBM
234.1TFC
324.9SAP
36.5TFC
0MWM
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
33.2TFC
132TFC
87.2TFC
134.8TFC
326.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC366233
custom_field_two
2
customer
LACSD
datetime
2019-04-29T22:28:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false